Alert Rule Builder & Alarm History
Rule: tag, condition, priority, recipients, escalation • History table with ack times
Create Alert Rule
Alarm History (Last 7 Days)
| Time | Priority | Tag | Description | Value | Limit | Acknowledged | Closed | Ack By | Dur. |
|---|---|---|---|---|---|---|---|---|---|
| 18 Nov, 07:14:22 | Critical | A-301.H2S_OUT | H₂S Scrubber Outlet High | 52 ppm | > 50 ppm | 07:15:10 | — | Ravi Sharma | 48s |
| 18 Nov, 06:30:00 | High | D-2.TEMP | Digester D-2 Temp Low | 37.8°C | < 38.0°C | 06:32:15 | 07:10:00 | Rajesh Kumar | 38m |
| 17 Nov, 22:10:05 | High | CAM-07 | Camera Feed Lost | No Data | > 30s | 22:12:30 | — | IT - Patel | 2m |
| 17 Nov, 14:22:10 | Critical | C-203.STATUS | Compressor C-203 Trip | STOPPED | RUNNING | 14:25:00 | — | Amit Singh | 3m |
| 17 Nov, 11:08:55 | Warning | D-2.FOAM | Digester D-2 Foam High | 28% | > 25% | 11:10:22 | 11:45:00 | Rajesh Kumar | 35m |
| 16 Nov, 18:45:10 | High | UPG.CH4_OUT | Product CH₄ Below Spec | 94.2% | > 95% | 18:48:00 | 19:30:00 | Ravi Sharma | 42m |
| 16 Nov, 09:15:40 | Warning | M-311 | Off-gas Meter Drift | +6.2% | > 5% | 09:18:00 | 10:00:00 | Auto (Value Normal) | 42m |
| 15 Nov, 23:10:22 | Critical | C-201.DISCHARGE_P | Compressor Discharge High | 262 bar | > 260 bar | 23:11:00 | 23:15:00 | Rajesh Kumar | 4m |
| 15 Nov, 16:30:00 | High | GH.LEVEL | Gas Holder Level High | 92% | > 90% | 16:32:00 | 17:00:00 | Ravi Sharma | 28m |
| 14 Nov, 19:55:40 | High | D-1.PH | Digester D-1 pH High | 7.85 | > 7.8 | 19:58:00 | 20:30:00 | Rajesh Kumar | 32m |
| 14 Nov, 11:20:15 | Critical | GAS_LEAK.COMP | Compressor House CH₄ Leak | 28% LEL | > 20% LEL | 11:21:00 | 11:45:00 | Safety - Singh | 24m |
| 14 Nov, 08:45:33 | Warning | D-2.LEVEL | Digester D-2 Level Low | 78% | < 80% | 08:48:00 | 09:30:00 | Rajesh Kumar | 42m |
Showing 12 of 147 alarms (7 Critical, 28 High, 52 Warning, 60 Info)
Avg Ack Time (Critical)
2 min 15s
Target: < 5 min
Avg Ack Time (High)
18 min 30s
Target: < 15 min
Alarms per Shift (Avg)
4.2
Down from 6.1 last month
Auto-Resolved %
23%
Return-to-normal auto-ack
Configured Alert Rules (42 Active)
| Rule Name | Tag | Condition | Priority | Recipients | Escalation | Status | Actions |
|---|---|---|---|---|---|---|---|
| H₂S Scrubber Outlet High | A-301.H2S_OUT | > 50 ppm | Critical | Shift Ops, Plant Mgr, Safety | 15 min → Safety | Active | |
| Digester Temp Low | D-*.TEMP | < 38.0°C | High | Shift Ops, Plant Mgr | 30 min → Plant Mgr | Active | |
| Digester Temp High | D-*.TEMP | > 40.0°C | Critical | Shift Ops, Plant Mgr, Safety | 5 min → Safety | Active | |
| Gas Holder Level High | GH.LEVEL | > 90% | High | Shift Ops | 30 min → Plant Mgr | Active | |
| Compressor Discharge High | C-*.DISCHARGE_P | > 260 bar | Critical | Shift Ops, Maint | 5 min → Maint Lead | Active | |
| Product CH₄ Below Spec | UPG.CH4_OUT | < 95% | High | Shift Ops, Plant Mgr | 15 min → Plant Mgr | Active | |
| Camera Feed Lost | CAM-*.HEARTBEAT | No data > 30s | High | IT, Safety | 30 min → IT Lead | Active | |
| Compressor Trip | C-*.STATUS | = STOPPED (unexpected) | Critical | Shift Ops, Maint, Plant Mgr | 5 min → Maint Lead | Active | |
| Gas Leak Detection | GAS_LEAK.* | > 20% LEL | Critical | All On-Site, Safety, Plant Mgr | Immediate → All | Active | |
| Digester pH Out of Range | D-*.PH | < 6.8 or > 7.8 | High | Shift Ops, Plant Mgr | 15 min → Plant Mgr | Active |